A CEC enclosure system
processor card over-temperature has been detected. Check for any environmental
issues before replacing any parts.
About this task
Note: Storage complex repair actions must always be managed from the management console. To replace any FRUs identified in this
procedure, use . If the FRUs are listed in the serviceable events, select them from there.
Procedure
- Is the ambient room temperature in the normal operating
range (less than 35 degrees C/95 degrees F)?
- No, notify the customer. The customer must lower the room
temperature so that it is within the normal range. Do not replace
any parts. This ends the procedure.
- Yes, continue to the next step.
- Are the front and rear of the CEC drawer, and the front
and rear rack doors free of obstructions that would impede the airflow
through the drawer?
- No, notify the customer. The system must be free of obstructions
for proper airflow. Clean the air inlets and exits in the drawer as
required. Do not replace any parts. This ends the procedure.
- Yes, continue to the next step.
- Are all of the fans, especially those at the back of the
power supply, functioning normally?
- No, replace any fans that are not turning or are turning slowly. This
ends the procedure.
- Yes, there are no environmental issues with the cooling of
the processors. This ends the procedure.