Checking customer receptacle voltage pins with customer CB off (plug in)

Procedure

  1. Prepare the multimeter to measure 1.0 V ac or less.
  2. Do the following:
    1. Measure the voltage between each pair of voltage pins ( A  to  B ,   B  to   C  and  C  to  A ) on the customer outlet.
    2. Measure the voltage between each voltage pin and ground (G) pin ( A  to (G),  B  to (G), and  C  to (G)) on the customer outlet.
    3. If the connector has five pins, measure the voltage between the neutral pin and ground pin. See Figure 3

    Did any voltage measure more than 1.0 V ac? Refer to Figure 1 or Figure 2 or Figure 3 for the location of the pins.

    Figure 1. Single-phase, 200 - 240 V, 60A, IEC60309 customer outlet pins
    Single-phase, 200 - 240 V, 60A, IEC60309 customer outlet pins
    Figure 2. Three-phase low voltage (200 - 240 V) phase-to-phase, 60A, IEC60309 customer outlet pins
    Three-phase low-voltage 200-240V phase-to-phase, 60A, IEC60309 customer outlet pins
    Figure 3. Three-phase high voltage (380 - 415 V) phase-to-phase, 30A, IEC60309 customer outlet pins
    Three-phase high-voltage (380 - 415 V) phase-to-phase, 30A, IEC60309 customer outlet pins