MAP1130 PPS Fan Normal and Failure Modes
The PPS fans have multiple operation modes for normal as well as failure conditions.
MAP1130 Section-1
Procedure
The operation of the PPS fans
is monitored and controlled by the microcode running in the PPS sequence
module. The fan speeds are controlled individually and vary for normal operation.
If an error condition occurs, a serviceable event is
created and reported.
The PPS fans
are controlled in 2 ways:
There are four fan speeds used:
- Stopped (0 rpm)
- Low (1860 rpm)
- Medium (2820 rpm)
- High (3800 rpm)
| Operating/Failure Condition | Top PPS Fan | Center PPS Fan | Bottom PPS Fan |
|---|---|---|---|
| Normal Mode | Low | Low | Low |
| Top PPS Fan failed | Failed | High | High |
| Center PPS Fan failed | High | Failed | High |
| Bottom PPS Fan failed | High | High | Failed |
| PPS to PPS Communication Failure | Medium | Medium | Medium |
| Battery charging in phase 1 | Medium | Medium | Medium |
| On Battery Mode (Booster not installed) | Stopped | Stopped | Stopped |
| On Battery Mode (Booster installed) | Stopped | Stopped | Stopped |
During PPS standby or fenced mode (208VDC and 5V/12V outputs are off), only the bottom and the center fans will operate.
| Operating/Failure Condition | Top PPS Fan | Center PPS Fan | Bottom PPS Fan |
|---|---|---|---|
| Normal Mode | Stopped | Low | Low |
| Center PPS Fan failed | Stopped | Failed | High |
| Bottom PPS Fan failed | Stopped | High | Failed |
| PPS to PPS Communication Failure | Stopped | Medium | Medium |