MAP2211 Power resource fenced but not isolated to a FRU

The SRCs listed in this topic indicate that either an RPC, primary power supply (PPS), or battery backup unit (BBU) device has been detected to be in the fenced state.

MAP2211 Section-2

Procedure

  1. SRC BE192500 indicates that a fenced RPC has been detected.
  2. Display open serviceable events for the storage facility. Other than the serviceable event that sent you to this MAP, are there any other related open serviceable events (BE19xxxx) that list an RPC as one of the FRUs?
    • Yes, exit this MAP and repair the related serviceable event. If the repair is successful, remember to close the serviceable event that sent you here.
    • No, contact your next level of support.

MAP2211 Section-3

Procedure

  1. SRC BE19251x indicates that a fenced PPS has been detected.
  2. Display open serviceable events for this storage facility. Other than the serviceable event that sent you to this MAP, are there any other related open serviceable events (BE19xxxx) that list a PPS as one of the FRUs?
    • Yes, exit this MAP and repair the related serviceable event. Close the serviceable event that sent you here.
    • No, contact your next level of support.

MAP2211 Section-4

Procedure

  1. SRC BE19252x indicates that a fenced battery enclosure has been detected.
  2. Display open serviceable events for this storage facility. Other than the serviceable event that sent you to this MAP, are there any other related open serviceable events (BE19xxxx) that list a battery module enclosure or battery module set as one of the FRUs?
    • Yes, exit this MAP and repair the related serviceable event. Close the serviceable event that sent you here.
    • No, contact your next level of support.