MAP2230 Overcurrent on DDM power boundary for both PPSs
Both PPSs have reported an overcurrent condition for one or more of the 5/12 VDC device power boundaries in the affected rack. The affected storage enclosures (front or back) will not be powered and access to customer data could be lost.
About this task
- Main DDM module in each PPS
- Optional DDM module in each PPS (if installed)
- Cable between the DDM power modules and the secondary device distribution bus bar
- Secondary device distribution bus bar mounted at the back center of the machine
- Primary device distribution bus bar which runs vertically between the device enclosures
- Bus bar jumpers between the primary and secondary device distribution bus bar
- Cable between each storage enclosure backplane and the primary device distribution bus bar
- Storage enclosure backplane
- FCIC logic cards
- DDMs