MAP2470 Powering off and on the storage facility from the management console
Use this MAP for instructions on how to power off and power on a storage facility using the management console.
MAP2470 Section-1 Power off or power on the storage facility
Procedure
- To power off the Model 94x, 95x, 96x, 98x (not 983) storage facility, go to MAP2470 Section-2 Power off the Model 94x, 95x, 96x, 98x (not 983) storage facility.
- To power on the Model 94x, 95x, 96x, 98x (not 983) storage facility, go to MAP2470 Section-3 Power on the Model 94x, 95x, 96x, 98x (not 983) storage facility.
- To power off the Model 983 storage facility, go to MAP2470 Section-4 Power off the storage facility (Model 983).
- To power on the Model 983 storage facility, go to MAP2470 Section-5 Power on the storage facility (Model 983)
MAP2470 Section-2 Power off the Model 94x, 95x, 96x, 98x (not 983) storage facility
Procedure
-
Ensure that the Local/Remote switch that is located on the local remote or System z® local remote switch card is set to
Remote. For Model 941, see Figure 1. For Model
951 or Model 961, see Figure 2.
For Model 98x, see Figure 3.
Figure 1. Local/Remote switch, Model 941
Figure 2. Local/Remote switch, Models 951, 961 
Figure 3. Local/Remote switch, Models 98x
- Power off the storage facility.
- From the navigation area, click Storage Facility Management > storage facility.
- From the bottom Task area, click Service Utilities > Storage Facility
Power Control. The Power Control window
opens.
Figure 4. Window: Power Control 
- In the upper left,
ensure that the Current Remote Power Control Mode is
set to Manual. Note: If the mode is not set to Manual, select Manual Power Mode from the Power Control Modes section.
- In the Change Storage Facility Power State section, click Power OFF Storage Facility, and then click OK.
- Click OK to confirm the update
for the Power Control Settings.
The storage facility begins the power off sequence.
- Wait a maximum of 10 minutes for the storage facility power
off sequence to complete.
The sequence is complete when the storage enclosures/DDMs are off, and the green LED is slow flashing on both CEC enclosure control panels.
Did the storage facility power off?
- Yes, go to step 5.
- No, go to the next step.
- The storage facility has
not powered off after waiting 10 minutes.
-
Wait a maximum of 30 minutes, and then contact your next level of support.
Notes:
- If the power-off sequence encountered a problem, it can take up to 90 minutes for a successful power-off.
- If the storage facility did not power off at all, it may be possible to check for and repair any open serviceable events related to rack power or the CEC enclosures.
- DO NOT force the power off by using the red UEPO switch or by any other method. If you force the power off, you need to contact your next level of support to help you recover the storage facility.
-
Wait a maximum of 30 minutes, and then contact your next level of support.
-
A complete power down (CPD) of the storage facility is a state where all components
are powered off and ready for external power to be removed. Do you need to do a complete power down
(CPD) of the storage facility?
- Yes, go to the next step.
- No, exit this MAP.
- Shut down the
management console as follows:
- From the navigation area, click HMC Management.
- In the right work area, go to the Operations section
and click Shut Down or Restart. The Shutdown or Restart window opens.
- Select Shutdown HMC, then click OK.
- Wait for the HMC to power off then go to the next step.
- Do you need to remove all customer power from
this storage facility?
- Yes, go to the next step.
- No, exit this procedure.
- If the storage facility
is a model 961, go to step 12.
If the storage facility is a model 98x, go to step 14.
If the storage facility is neither a model 961 or model 98x, go to step 9. - At the rear of
each rack in the storage facility, switch
off the mainline power CB00
(Figure 5) on both primary power
supplies (PPS). Figure 5. Rear view of PPS showing CB00 
- Verify that all input power has been removed from each
rack. At the front of both PPSs in each rack, ensure the
AC INPUT GOOD LED indicator is off.
Note: If the LED is lit, CB00 is not switched off.In Figure 6, the Model 941/94E is shown; the Model 951/95E is similar.Figure 6. LEDs on the PPS (front) 
- Go to step 16.
- At the rear
of each rack in the storage facility, set the main line switch CB1
(Figure 7) to Off (down) on both DC-UPS. Figure 7. DC-UPS DC supply unit (DSU) 
-
Verify that all input power has been removed from each rack. At the rear of both DC=UPSs in
each rack, ensure the
LOCAL AC (input) LED indicator is off. See Figure 7.
Note: If the LED is lit, CB1 is not switched off.Go to Step 16.
-
For model 98x, single-phase power, at the rear of each rack in the storage facility, set the main line
switch CB1 (Figure 8) to Off (down) on both DC-UPS.
For model 98x, three-phase power, at the rear of each rack in the storage facility, set the main line switch CB1
(Figure 9) to Off (down) on both DC-UPS.
Figure 8. DC-UPS DC supply unit (DSU), Models 98x, single-phase power
Figure 9. DC-UPS DC supply unit (DSU), Models 98x, three-phase power
Figure 10. LEDs on the DC-UPS DC supply unit (DSU) (Models 98x, single-phase power)
-
Verify that all input power has been removed from each rack. At the rear of both
DC-UPSs in each rack, ensure the LOCAL AC (input) LED indicator is off. See
2 , Figure 9 or
5 , Figure 10.
Note: If the LED is lit, CB1 (Figure 8) is not switched off.
- If you plan to disconnect the mainline power cords, ensure the customer has switched off the circuit breaker for each mainline power cord to be disconnected.
MAP2470 Section-3 Power on the Model 94x, 95x, 96x, 98x (not 983) storage facility
Procedure
- If the storage facility
is a model 961, go to step 4.
If the storage facility is a model 98x, go to step 6.
If the storage facility is neither a model 961 or a model 98x, go to step 2. - Observe the front of each rack in the
storage facility. Are the LEDs for AC INPUT GOOD
and UEPO LOOP GOOD
on each PPS lit solid? See Figure 6.
- Yes, go to the next step.
- No. A rack can power on successfully with only one of the
two redundant PPSs operational. However, it is best to have both PPSs
in each rack operational before you power on the storage facility.
Do the following:
- At the rear of the rack, ensure that the mainline power cables are connected to the PPS and also to the customer power source.
- Ensure that the customer circuit breaker for each mainline power cable source is set to on.
- At the rear of each PPS, ensure that each mainline power CB00 is switched to on (up).
- If you cannot find the problem and only one PPS in the rack is not operational, wait and fix it after the storage facility is powered on. There should be an open serviceable event for the problem.
- Go to step 7.
- Observe
the rear of each rack in the storage facility. Is the LOCAL AC (input)
LED indicator on each DC-UPS lit solid?
See Figure 7.
- Yes, go to the next step.
- No. A rack can power on successfully with only one of the two redundant DC-UPSs operational.
However, it is best to have both DC-UPSs in each rack operational before you power on the storage
facility. Do the following:
- At the rear of the rack, ensure that the mainline power cables are connected to the DC-UPSs and also to the customer power source.
- Ensure that the customer circuit breaker for each mainline power cable source is set to on.
- At the rear of each DC-UPS, ensure that each main line switch CB1 is switched to on (up).
- If you cannot find the problem and only one DC-UPS in the rack is not operational, wait and fix it after the storage facility is powered on. There should be an open serviceable event for the problem.
- Go to step 7
-
Observe the rear of each rack in the storage facility. Is the LOCAL AC (input) LED indicator on
each DC-UPS lit solid? See Figure 9 or Figure 10.
- Yes, go to the next step.
- No. A rack can power on successfully with only one of the two redundant DC-UPSs operational.
However, it is best to have both DC-UPSs in each rack operational before you power on the storage
facility. Do the following:
- At the rear of the rack, ensure that the mainline power cables are connected to the DC-UPSs and also to the customer power source.
- Ensure that the customer circuit breaker for each mainline power cable source is set to on.
- At the rear of each DC-UPS, ensure that each main line switch CB1 (Figure 8) is switched to on (up).
- If you cannot find the problem and only one DC-UPS in the rack is not operational, wait and fix it after the storage facility is powered on. There should be an open serviceable event for the problem.
- Ensure that the management console has powered on. If not, manually power it on.
- Power on the storage facility.
- From the navigation area, click Storage Facility Management > storage facility.
- From the bottom Task area, click Service Utilities > Storage Facility
Power Control. The Power Control window
opens.
Figure 11. Window: Power Control 
- At the top of the screen, ensure that the Current
Power Control Mode is set to Manual.
Note: If the mode is not set to Manual, select Manual Power Mode from the Power Control Modes section.
- In the Change Storage Facility Power State section, click Power ON Storage Facility, and then click OK.
- Click OK to confirm the update
for the Power Control Settings.
The storage facility begins the power-on sequence.
The power-on process can take up to 30 minutes for the LPARs to be ready for customer use.
- Remember to use the Power Control Modes to restore the mode back to its original setting.
MAP2470 Section-4 Power off the storage facility (Model 983)
Procedure
-
Power off the storage facility.
- From the navigation area, click Storage Facility Management > storage facility.
-
From the bottom Task area, click Service Utilities > Storage Facility
Power Control. The Power Control window
opens.
Figure 12. Window: Power Control 
-
In the upper left, ensure that the Current Remote Power Control Mode is
set to Manual.
Note: If the mode is not set to Manual, select Manual Power Mode from the Power Control Modes section.
- In the Change Storage Facility Power State section, click Power OFF Storage Facility, and then click OK.
-
Click OK to confirm the update for the Power Control Settings.
The storage facility begins the power-off sequence.
-
Wait a maximum of 10 minutes for the storage facility power off sequence to
complete.
The sequence is complete when the green LED is slow flashing on both CEC enclosure control panels.Did the storage facility power off?
- Yes, go to step 4.
- No, go to the next step.
-
The storage facility did not power off after 10 minutes.
-
Wait a maximum of 30 minutes, and then contact your next level of support.
- If the power-off sequence encountered a problem, it can take up to 90 minutes for a successful power-off.
- If the storage facility did not power off, it might be possible to check for and repair any open serviceable events related to rack power or the CEC enclosures.
- DO NOT force the power off by unplugging the mainline power cables or by any other method. If you force the power off, you need to contact your next level of support to help you recover the storage facility.
-
Wait a maximum of 30 minutes, and then contact your next level of support.
-
A complete power down (CPD) of the storage facility is a state where all components
are powered off and ready for external power to be removed. Do you need to do a complete power down
of the storage facility?
- Yes, go to the next step.
- No, exit this MAP.
-
Shut down the management console as follows:
- From the navigation area, click HMC Management.
- In the right work area, go to the Operations section and click Shut Down or Restart. The Shutdown or Restart window opens.
- Select Shutdown HMC, then click OK.
- Wait for the HMC to power off, then go to the next step.
- Disconnect the management console in use from the keyboard/display and then connect to
the other management console.
- Each management console has one VGA and one USB cable exiting the management enclosure cable management arm at the rear of rack. The end of each cable is uniquely labeled. See Table 1.
- Locate the VGA cable and USB cable coming from the keyboard/display and disconnect them.
- Connect the keyboard/display cables to the VGA and USB cables for the other management console.
Table 1. Management console cable labels Management Console Cable Label Text Label Color MC1 - Display MC1-VGA Black text on white label MC1 - Keyboard MC1-KYBD Black text on green label MC2 - Display MC2-VGA Black text on white label MC2 - Keyboard MC2-KYBD Black text on green label - Shut down the other management console.
-
Do you need to remove all customer power from this storage facility?
- Yes, go to the next step.
- No, exit this procedure.
-
Remove all input power. The UPS will automatically go on battery for up to 5 minutes and then
will power off and the UPS control panel will go dark.
- If the mainline power cables are connected to source power that has individual circuit breakers or a switch, ensure they are switched off now.
- Unplug the mainline power cables from the source power connectors.
- Unplug the mainline power cables from the UPS from the UPS J10 connectors (lower
left). See Figure 13.
Figure 13. Location codes for the UPS (Model 983), rear view 
- Exit this MAP.
MAP2470 Section-5 Power on the storage facility (Model 983)
Procedure
-
At the front of the rack, locate both UPS (E61 and E62). See Figure 14.
Figure 14. Locations, storage controller enclosures (Model 983)
-
Observe the UPS control panel Output status LED indicator. See Figure 15.
Use the following condition that applies.- The indicator is lit on both UPS. Go to step 3.
- The indicator is lit on one UPS and not lit on the other UPS. The storage facility can power
on using one UPS. Go to step 3.Note: The UPS that is not lit can be repaired later by using MAP2870 UPS visual symptoms.
- The indicator is not lit on both UPS. Correct the problem by using MAP2870 UPS visual symptoms. Then return to MAP2470 Section-5 Power on the storage facility (Model 983) step 2.
Figure 15. Locations, UPS control panel (Model 983)
- Ensure that the management console has powered on. If not, power it on.
-
Power on the storage facility.
- From the navigation area, click Storage Facility Management > storage facility.
-
From the bottom Task area, click Service Utilities > Storage Facility
Power Control. The Power Control window
opens.
Figure 16. Window: Power Control 
-
At the top of the screen, ensure that the Current Power Control Mode is
set to Manual.
Note: If the mode is not set to Manual, select Manual Power Mode from the Power Control Modes section.
- In the Change Storage Facility Power State section, click Power ON Storage Facility, and then click OK.
-
Click OK to confirm the update for the Power Control Settings.
The storage facility begins the power-on sequence.
The power-on process can take up to 30 minutes for the LPARs to be ready for customer use.
- Use the Power Control Modes to restore the mode back to its original setting.