MAP2621 SRC BE19394x Waiting for battery service module (BSM) sets to achieve 90% charge

The rack battery service module (BSM) sets are being charged but have not yet achieved the 90% minimum charge to allow the storage facility to be used.

MAP2621 Section-1

Procedure

  1. Determine which rack in the storage facility is reporting the battery charge condition. Reference the last character of the SRC field in the serviceable event that sent you to this MAP. The last character identifies the rack.
  2. Are there any open serviceable events related to the DC-UPS DSU or battery service module (BSM) sets in this rack?
    • Yes, exit this MAP and repair those serviceable events.
    • No, go to the next step.
  3. There are no hardware problems at this time. The battery modules are charging normally and must achieve 90% of their maximum charge before the code will allow the storage facility to be used. There is no utility option to display the battery charge percentage, so you should retry each operation that gave the error in 30 to 60 minutes.
    • Wait a maximum of 3 hours for the 80% battery module charge to be achieved.
    • If the error condition does not go away after 3 hours, check once again for related open serviceable events to repair and, if there are none, return to the serviceable event that sent you here and replace the BSM set listed in the FRU list. Refer to Figure 1. For BSM layout and location in bottom, front rack for models 98x, see Figure 2 and Figure 3.
    Figure 1. Base rack locations, front and rear
    Base rack locations, front and rear
    Figure 2. Battery service module (BSM) set locations (Models 98x single-phase power) (front)
    Battery service module (BSM) set locations (Models 98x) (front)
    Figure 3. Battery service module (BSM) set locations (Models 98x three-phase power) (front)
    Battery service module (BSM) set locations (Models 98x, three-phase power) (front)