PWR1909
A power supply load fault is occurring in an I/O enclosure.
PWR1909 Section-1
About this task
An I/O enclosure is reporting an overcurrent fault which
is detected by the power supplies. Even though it is likely that only
one FRU is causing the problem, the actual failing FRU is not known.
Because it can take about one hour to replace a FRU, it would take
too much time to replace each possible FRU one at a time. Because
this error condition is so rare, you are directed to replace all possible
FRUs in the I/O enclosure at the same time. The FRUs to be replaced
are:
- I/O enclosure backplane assembly
- Device adapter cards
- Host adapter cards
- I/O enclosure RIO card
- I/O enclosure power supplies
- I/O enclosure fan (assembly)