11001540 11001540

Explanation

Detected AC loss.

Response

Before replacing any parts, verify that the AC input voltage is correct. Follow the instructions for the items listed in the FRU List.

Problem determination

The system might have experienced an AC Power Loss external to the system such as utility or building power and the system might have recovered.
  1. If there was a utility, building or room power loss that would have affected the system at the same time this SRC was reported then you can ignore and close this event. No service is required. Otherwise continue with the next step in this procedure.
  2. Ensure the line cords are properly connected and seated on both ends. For help in locating the line cords of the power supply reporting this problem use the location code in the serviceable event or the symbolic FRU in the failing items list below.
  3. If the system was just installed or moved, verify the AC input voltage is correct.
  4. If the problem is not resolved then report this problem to your service provider.

Failing Item