Exchange the RPC card to DC-UPS cable
Before you begin
Use approved ESD procedures to prevent damage.
Attention:
- This procedure is not a stand-alone procedure. Customer disruption and damage to the hardware might occur when microcode and power boundaries are not in the proper conditions for this service action.
- If a serviceable event FRU repair directed you to this procedure, the microcode and power boundaries are already set.
- If a serviceable event FRU repair did not direct you to this procedure, see MAP1230 Replace a FRU without using a serviceable event.
Notes:
- All the cables and FRUs to be removed must be uniquely identified so they can be reinstalled correctly.
- If an installed earthquake resistance kit prevents you from accessing this FRU, refer to MAP1600.
Remove the RPC card to DC-UPS cable
Procedure
Install the RPC card to DC-UPS cable
Procedure
- Route the cable.
- Connect the cable to the RPC card connector.
- Connect the cable to the J6 or J7 connector as appropriate on both the upper and lower DC-UPS.
- Install the cable retention hardware.
- Exit this service information center parts exchange procedure and return to the procedure that sent you here.