Exchange the I/O enclosure (2U) adapter (PCN)

About this task

Icon for electrostatic discharge wrist strapUse approved ESD procedures to prevent damage.

Attention:
  • This procedure is not a stand-alone procedure. Customer disruption and damage to the hardware might occur when microcode and power boundaries are not in the proper conditions for this service action.
  • If a serviceable event FRU repair directed you to this procedure, the microcode and power boundaries are already set.
  • If a serviceable event FRU repair did not direct you to this procedure, see MAP1230 Replace a FRU without using a serviceable event.
Notes:
  • All the cables and FRUs to be removed must be uniquely identified so they can be reinstalled correctly.
  • If an installed earthquake resistance kit prevents you from accessing this FRU, refer to MAP1600.

Remove the I/O enclosure (2U) adapter (PCN)

Procedure

  1. To locate this FRU, take one of the following options and then return here and continue to replace the FRU:
    • If this FRU has a FRU identify indicator, use the FRU identify indicator, which is listed in MAP1240 Locating FRUs by using identify indicators. If not, use the location code.
      Note: There might be cases where the FRU failure or fencing conditions prevent the FRU LED indicator from being lit even if the FRU has power.
    • Use the location code, which is listed in MAP1245 Finding FRUs by using location codes.
    • If there is no FRU identify indicator or location code, you were sent here by an isolation MAP or symbolic FRU procedure. Use the information in that procedure and the figures in this procedure to locate the proper part to exchange.
  2. Most, but not all, FRUs have identify indicators. Use the flashing amber or solid blue FRU identify indicators to ensure that you are working on the correct enclosure or FRU.
  3. At the rear of the management enclosure, ensure that the two PCN (Power Control Network) cables (P1-C9-T1, P1-C9-T2) are properly labeled and then disconnect them. See Figure 1 and Figure 2.
    Figure 1. Location codes, I/O enclosure (2U) (rear) (model 983)
    I/O enclosure (2U) locations (front) (model 983)
    Figure 2. Location codes, I/O enclosure (2U) adapter (PCN)
    Location codes, I/O enclosure (2U) adapter (PCN)
  4. Unlatch the blue lever at the right of the card and then slide the card out of the enclosure.

Install the I/O enclosure (2U) adapter (PCN)

Procedure

  1. Slide the adapter in and use the blue lever to latch it in place.
  2. Connect the PCN cables to ports T1 and T2.
  3. Exit this service information center parts exchange procedure and return to the procedure that sent you here.