Exchange the I/O enclosure power supply
Before you begin
Use approved ESD procedures to prevent damage.
Attention:
- This procedure is not a stand-alone procedure. Customer disruption and damage to the hardware might occur when microcode and power boundaries are not in the proper conditions for this service action.
- If a serviceable event FRU repair directed you to this procedure, the microcode and power boundaries are already set.
- If a serviceable event FRU repair did not direct you to this procedure, see MAP1230 Replace a FRU without using a serviceable event.
Notes:
- All the cables and FRUs to be removed must be uniquely identified so they can be reinstalled correctly.
- If an installed earthquake resistance kit prevents you from accessing this FRU, refer to MAP1600.
Remove the I/O enclosure power supply
About this task
Attention: Power supplies are hot-pluggable FRUs.
Only remove one power supply at a time.
Note: You need 5.5 mm sockets to remove hex
head screws for this FRU.
or
on the I/O enclosure power supply must be
lit before going to the next step. This will ensure that the I/O enclosure
remains powered on when the failing power supply is removed. If the
power good LED is not lit, DO NOT CONTINUE. Instead
and
input power to power supply
and
identify for I/O enclosure power supply